Hired a licensed electrician to do a meter panel swap which did not go well.
I verified that NEMA requirements are to keep the wires at a minimum within the wiring gutter. Not sure what NEC has to say on the subject since my code book is from 1984.
-
KMS Woodworks on Mar 16, 2011I think the best option here would be to install a new longer 4/0 feed from your tie point at the masthead into this box. Looking at your photo It already looks like you have some breakers in there? are those breakers feeding your main breaker panel?Helpful Reply
-
-
Darby C on Mar 16, 2011This picture appears to be the whole house cut off. This is on the outside of the house with only one breaker that cuts off the entire house. Am I correct that the wires that you are showing in the picture are going to the panel inside the house? It looks like it is wired correctly, based on what I can see from the picture.Helpful Reply
-
-
Stephen on Mar 16, 2011Darby your are correct the 4/0 wire is going to a sub panel for the house. The existing breakers are for the sub panel in the house and main breaker for the panel. This panel has spaces for two 240 volt breakers and a slim 120 volt breaker. The hot leg is ran across the space where those breakers should be installed, which defeats the reason for replacing the panel in the first place. The panel was replased because we needed to add a 2nd sub panel and a connection for a hot tub requiring the space the hot leg is routed through.Helpful Reply
-
-
Darby C on Mar 16, 2011I believe that you can splice the lines. It may cost just as much to run a new piece of wire to the panel, if you have access to the entire wire. There are special connectors that are made for this type of thing. And then you have to put shrink tape on them.Helpful Reply
-
-
Stephen on Mar 16, 201150 feet of 4/0 service is about $200, and a half dozen holes in the celling and walls, I think I will go with the splice since the electrical inspectors seem to accept a splice in the box.Helpful Reply
-
-
Darby C on Mar 16, 2011If the inspector is O.K. with it then I would too. My power company was going to splice my main in the box when I had to replace my meter base, so you should be fine.Helpful Reply
-
-
Argo Electrical Services on Feb 04, 2013Stephan they make a Polaris Lug. It is heavily insulated lug. You can attach another longer piece of 4/0. This will allow you to route the wire around the outside of the can. Even the power company will splice their feeders if they are short. It's very common. You can purchase the Polaris Lugs at a real Electrical Supply House. I use Arc Electrical in Cumming GA. Ask for Todd or Mike..Tell them I sent you. They will treat you right. If you need direction during the install call me @ 678-682-0387.. On the houseHelpful Reply
-
-
Argo Electrical Services on Feb 04, 2013Here they are.. You tighten them with allen wrenchs...Make sure you coat your wire with Nolox!Helpful Reply
-
Related Discussions
Best way to make your driveway look like stone with paint?
Several years ago there was a DIY video on how to do this but can't fine it.
Are gray walls here to stay or are they on their way out?
Hey everyone,Gray wall color has long been a favorite choice due to its versatility, modern appeal, and ability to complement a wide range of design styles.But the qu... See more
Which mattress firmness do you prefer: soft or hard?
Finding the perfect mattress can be a game-changer for your sleep quality and overall health.So, we're curious: When it comes to mattress firmness, what’s your pref... See more
Toilet: Rumbling / Vibrating Noise when FILLING up (SMOOTH when flush)
When flushing the toilet, no problem, smooth flush like all others, no issues. (My 1st inclination of the noise when filling up was a clogged toilet, but it flushes q... See more
Clean grout hard (iron) water stains?
We have a shower that has laminate side and flooring. The areas were grout is has turned orange/Black. I have used vinegar applied with toothbrush, Granite Gold grout... See more
How do I remove super glue from a rubber floor mat?
I spilled glue on my rubber floor mat and have tried alcohol, soap, goop and some other things, but nothing took it all away.
How to remove cigarette smoke smell from my sewing machine?
I just bought a used sewing machine. Brought it home and wiped it down with Clorox wipes and they were dirty. Now the machine reaks of cigarette smoke. I tried vinega... See more