As per code, What size of electric cable(14/3 or 12/3) is allowed to wire receptacles and lighting?
-
Woodbridge Environmental Tiptophouse.com on Jan 25, 2012Both. However its really 14/2 and 12/2 Normally we do not count the uninsulated ground wire in the numbers. However they do use three wires in three way switches or where they want to run two circuits to a location and use only one ground back. Not sure if they still use this practice or not, but years ago this was common occurrence in an effort to save money on wire. Normally 14 wire is used for outlets or lamps, with the exception of areas such as baths laundries and kitchens where they want to use a 20 amp breaker then they use 12 wire. Or where they are installing very large fixtures which require a larger breaker because of the load that they require. Kitchens require two 20 amp circuits for small appliances, And if you use a three wire where there are two circuits with one ground wire going back to panel, The breakers for the two circuits must be tied on handle so both are turned off at same time should you need to service one of the circuits or if a short occurs.Helpful Reply
-
-
Yamini LEED AP at Urbanmotifs on Jan 25, 2012Thank you Woodbridge, I didn't find this in my Code Check book, I appreciate your answer.Helpful Reply
-
-
ElectraMedics Electrical Services on Jan 26, 2012Kitchens Outlets, Bathroom Outlets, and Dining Outlets must be 12/2 or 20 amps. All other lighting and outlets are generally installed with 14/2 15 amps. 14/3 is only used to add 3 way switches or ceiling fans.Helpful Reply
-
-
Hewitt Remodeling Services LLC on Jan 26, 2012Here is an add-on question. Are you ever allowed to "mix" the 12 gauge with the 14 gauge..? if so, is there a difference in the order it can be used?Helpful Reply
-
-
Woodbridge Environmental Tiptophouse.com on Jan 26, 2012Its my understanding that you can mix, but you must be sure that the breaker is sized for the smaller size wire. It is not really something that you would ever see done in new construction, but found quite a lot in remodels. And I would suggest that it not be done, but there is no harm by using a bigger wire then what the breaker is designed to protect.Helpful Reply
-
-
ElectraMedics Electrical Services on Jan 26, 2012you can use 12 where 14 is needed but not the other way around. It is always okay to upsize the wire not downsizeHelpful Reply
-
-
LandlightS on Jan 26, 2012The inspectors in Atlanta and Fulton county do not allow any downsizing of wire..if it's a 20 amp circuit with 12/2, it's12/2 to the dead end device. As a general rule, all outlet circuits should be 20amp and lighting circuits should be 15 amp.Helpful Reply
-
Related Discussions
What should I do with this rusty bucket?
I love rusty junk. So when I saw this bucket at a yard sale I liked it too much to pass it up. The question now is, what do I do with it? My only thought is to turn i... See more
Which room would you pick for a room makeover in your home?
We're curious, if you could redesign any room in your home, which is the room you would choose?Whether it's your cozy living room, your bustling kitchen, or even your... See more
How to find out the value of antique furniture
My husband and I are looking to sell his grandmother's dining room set but, we have no idea what to ask for it. We could not find any markings as to who made it, all ... See more
How can I get the actual grass clippings out of the sock?
Help - I have tried everything! I can't get the actual grass cuttings out of my sons socks!Best socks!If you need new socks Dickie's moisture control socks are the o... See more
How do I remove the stubborn stains from gas stove?
How do I remove the stubborn stains from gas stove?